Flexa 200/400-400

Three Phase Uninterruptible Power Supply 20kVA – 640kVA

Flexa 200 is a compact and modular UPS using a smart technology 3P input/output. It provides a pure sine wave with 96% conversion efficiency. Our technology offers a 0ms transfer time (from grid to batteries), integrates the static switch function, limited boost capability (to trigger downstream breakers while protecting upstream ones) and is easy to maintain (24kg hot-swappable modules):

Always powered

Flexa 200 operates without master/slave configuration, includes a redundant communication BUS and is IPC9592B certified. Efficient battery management makes it possible to always be ready to secure loads thanks to fast battery charging (up to 17kW), low ripple voltage and different charging modes.

Flexibility

Flexa 200 can be configured in 50Hz or 60Hz and also exists in 3P to 1P topology (Flexa 200 – 400/230). Cabinets can be customized on-demand, modules can be integrated into third-party cabinets or reused existing ones. Everything to be as flexible as possible.

Applications

Flexa 200 is used in many applications to protect IT loads in data centers and edge computing sites. Flexa 200 is also used and suitable for industrial, renewables, oil and gas, power utilities and in harsh environment (up to IP54).

Specifications Table

Flexa 200 – 400/400Module60 kVA/kW160 kVA/kW200 kVA/kW640 kVA/kW
General
Module Part NumberT451970112
EMC (immunity)EN 61000-4-2 / EN 61000-4-3 / EN 61000-4-4 / EN 61000-4-5 / EN 61000-4-6 / EN 61000-4-8
EMC (emission) (class)EN 55022 (A)
SafetyEN 62040-1-1
EN62040-3 performance levelVFI-SS-111
MTBF / Cooling240 000 hrs / Forced
True Redundant Systems – compliant3 disconnection levels on AC out and DC in power ports / 4 disconnection levels on AC in port
RoHSCompliant
VibrationGR63 office vibration 0 to 100 hz-0.1 g / transport vibration 5-100 Hz 0.5 g 100 to 500 hz-1.5 g / Drop test
Operating conditionsDesigned for installation in an IP20 or IP21 environment.
When installed in a dusty or corrosive environment, appropriate measures (air filtering, …) must be taken.
Altitude above sea without de-rating< 1500 m / derating > 1500 m – 0.8 % per 100 m
Ambient / storage temperature / relative humidity-10 to 40 °C / -40 to 70 °C / 95%, non-condensing
Material (casing)Coated steel-ALU ZINC-Front plate coated black RAL9005
Power
DC Input Data
Nominal voltage (DC)408 Vdc (204 cells VRLA) or 336 cells (NiCd)
Voltage range (DC)336 Vdc to 490 Vdc
Nominal current (at 408 Vdc)52 A156 A416 A520 A1664 A
Maximum input current (for 5 second) / voltage ripple67 A / < 400m Vrms201 A / < 400m Vrms 536 A / < 400m Vrms 670 A / < 400m Vrms2144 A / < 400m Vrms
Input voltage boundariesUser selectable with T4S interface
AC Input Data
Nominal voltage (AC)3×380 / 400 / 415+Neutral 5 wires for 3 phases
Voltage range (AC)150 Vac to 275 Vac Line to Neutral (derating 150 to 220 Vac)
Conformity range before transfer to DCAdjustable
Power factor> 99%
Frequency range / synchronization range50 or 60 Hz (selectable) / range 30 to 70 Hz adjustable
AC Output Data
Efficiency (Typical): AC to AC / DC to AC96% / 96% (certfiied by SGS at 45% load)
Nominal voltage (AC*)3×380 / 400 / 415+Neutral 5 wires for 3 phases
Frequency / frequency accuracy50 – 60 Hz / 0.03 %
Nominal Output power (VA) / (W)20 kVA / 20 kW60 kVA / 60 kW160 kVA / 160 kW200 kVA / 200 kW640 kVA / 640 kW
Short time overload capacity (@PF 0.9)150% – 15s | 130% – 30s | 120% – 60s | 110% permanent
Admissible load power factorFull power rating from 0 inductive to 0 capacitive
Total harmonic distortion (resistive load)< 1.5 %
Load impact recovery time0.4 ms
Turn on delay20 s to 40 s depending on the number of module installed
Nominal current at 230 Vac per phase29 A87 A232 A290 A928 A
Crest factor at nominal power2.8 : 1
Short circuit clear  up capacity5 x In for 20 msec – Available while Mains is available at AC input port , with magnitude control and management
Short circuit current on battery, per phase53 A 20 mS – 38 A Rms 15 Sec.
Internal temperature management and switch offYes
In Transfer Performance
Max. voltage interruption / total transient voltage duration (max)0 s / 0 s
Signaling & Supervision
DisplaySynoptic LED
Alarms output / supervisionDry contacts on T4S / MODBUS, TCP-IP, SNMP
Remote ON / OFFOn rear terminal of the shelf via T4S
Cabinets
Dimensions (WxHxD) mm **19” x 3U x 515 mm600 x 2100 x 8001200 x 2100 x 8002400 x 2100 x 800
Number of CabinetsNA1124
* Operation within lower voltage networks leads to de-rating of power performances.
** Other cabinet heights on demand

Ask for Assistance

Selecting the right power supply for your application is not a small task. Let our technical sales engineers guide you through the process of choosing the right solution for your needs.

Below some parameters usually required to size and select the right power supply:

  • Power & control requirements
  • Output & Input Voltage / Multioutput Voltage / Variable Voltage
  • Redundancy level
  • Mounting
  • Inrush Current
  • Environmental specifications (Temperature, altitude, vibration, shock)
  • Specific Industries Standards (Railway, Military, Medical)
  • Terminals

Contact Our Team

Contact our team of experienced engineers to discuss your unique power conversion and backup needs. We offer a wide range of highly reliable components that can be integrated and customized to create a solution that meets or exceeds your requirements.

For power automation systems please contact us at power.systems.automation@heliosps.com.au

You may also like...