The 9840, 9740 and 2045 series is part of a family of 3-Step chargers from 10 – 240 watts. These 3-step chargers are designed for Cyclic applications, where the need to re-charge a battery as quickly as possible is the main requirement.
The charger operates in a boost/timer mode for approximately 4 ½ hours. At the end of the timer period, the charger will return to a Float Voltage level, where it can be left on indefinitely. The timer is automatically activated when the AC power is switched on.
Model | Output Cycle | Voltage Float | Current A | Battery Capacity |
9740 – 12 | 14.7V | 13.7V | 10A | 40 – 400AH |
9740 – 24 | 29.4V | 27.4V | 5A | 20 – 200AH |
9740 – 36 | 44.1V | 41.1V | 3.3A | 15 – 150AH |
9740 – 48 | 58.8V | 54.8V | 2.5A | 10 – 100AH |
9840 – 12 | 14.7V | 13.7V | 5A | 20 – 120AH |
9840 – 24 | 29.4V | 27.4V | 2.5A | 10 – 60AH |
2045 – 12 | 14.7V | 13.7V | 20A | 100 – 1000AH |
2045 – 24 | 29.4V | 27.4V | 10A | 50 – 500AH |
2045 – 36 | 44.1V | 41.1V | 6.7A | 35 – 350AH |
2045 – 48 | 58.8V | 54.8V | 5A | 25 – 250AH |
Input Voltage | 230 VAC (190 – 264 VAC) |
Output Power | 75 – 240 watts |
Output Voltage | 12V models: 13.7V float, |
24V models: 27.4V float | |
36V models: 40.8V float | |
48V models: 54.8V fl0at | |
Efficiency: | Typically 81% |
Load Regulation | ±1% |
Line Regulation | ±0.5% |
Operating Temp | -25°C to +50°C |
Dimensions | 9840: 158 x 171 x 54mm. (9840) 9740: 184 x 171 x 54mm. (9740) 2045: 215 x 186 x 64mm. (2045) |
Weight | 1.27Kg (9840) , 1.5Kg (9740) , 2.4Kg (2045) |