SR100B – Smartcharger 100W Fast and Safe Recharging for lead acid batteries

Brand: HELIOS POWER SOLUTIONS

SKU: HPS-PS-BATTERY-CHARGERS-SR100B
This product is available globally.
  • Ideal for cyclic recharging applications.
  • Suitable for all types of lead acid batteries.
  • Automatic temperature compensation and relay alarm options.
  • Boost charge can be programmed to be manually initiated (eg. for equalisation charge).
  • Can safely be left permanently connected to the battery, will maintain ‘float’ charge.

Description

The SR SmartCharger is designed to recharge your battery in the shortest practicable time with programmable parameters to suit your specific application. Smartsharger 100W.

SERIES TABLE

ModelOutput Voltage¹ (float)Output Voltage¹ (max boost)Output Current (continuous)Min – Max Battery Size2
SR100B1213.814.76.7A24  – 70 Ah
SR100B2427.629.43.3A12 –  40 Ah
SR100B3641.444.12.2A9 – 25 Ah
SR100B4855.258.81.7A6 – 20 Ah
¹ May be adjusted to suit battery specifications
²  Check manufacturer’s recommendations

SPECIFICATIONS TABLE

ELECTRICAL
InputSTANDARD: 180V – 264VAC
OPTIONAL: 88V – 132VAC
Frecuency45-65Hz
FusingInternal AC input fuse
Isolation1KV DC input – output / earth
Efficiency> 85%
Inrush current<30A, 1.8ms
Output power100W
Output voltagesRefer to the model table
Voltage adj. rangeApprox 95 – 105% of V nominal
Temp. CompensationTemperature sensor on 1.7m lead with
adhesive pad:  -4mV / °C / cell ±10%
Current LimitStraight line current limit profile (output side)
Output ProtectionAutomatic shutdown if battery leads reversed
or short circuit on output
Line regulation<0.04% over input range
Load regulation<0.5% open circuit to 100% load
Noise<0.3%
Transient response200mV over / undershoot,
load step 20-100%, 400us settling time
Hold-up time15 – 20 ms (nom. – max. Vin) without  battery
FEATURES
LED IndicationBOOST:  Red
FLOAT:  Green
Factory Programmable parameters (default settings shown in brackets; please note that some parameters are interdependent of each other)Start up in boost mode (Boost)
Current terminated boost  (Yes)
Current initiated boost  (Yes)
Start in boost on mains return (Yes)
Pre-boost state timer (1 minute)
Max boost charge time (24 hours)
Pre-float state timer (1 minute)
Resume prior state upon mains return timer (10 minutes)
Resume on boost charge upon mains return  (24 hours)
Delay before mains fail recognition (5 mins)
ENVIRONMENTAL
Operating temperatureStandard: 0  to 50 °C ambient at full load ,De-rate linearly >50 °C to no load @ 70 °C
Storage temperature -10 to 85 °C ambient
Humidity0 – 95% relative humidity non-condensing
CoolingNatural convenction

View Datasheet