24VDC 20A Redundancy Module Din Rail , allows redundant operanting with easy system integration

SPECIFICATIONS TABLE

INPUT VOLTAGE: 24VDC   (21-28)
NUMBER OF INPUTS: Two  (A & B)
INPUT CURRENT: Combined for two inputs, A & B @ 20A
OUTPUT CURRENT: Maximum 20A total
EFFICIENCY: 97%
VOLTAGE DROP: Input – Output 0.5 VDC
REVERSE OUTPUT VOLTAGE 35 VDC
PROTECTION: Overload: None
Overvoltage: None
INPUT VOLTAGE MONITOR: A & B inputs: LED indicator
A & B inputs: DC OK relay contact Alarm
INPUT VOLTAGE ALARM: 19.2 VDC ±1%  Low Alarm
30 VDC ±5%     High Alarm
RELAY CONTACTS: 28VDC  1A  or 120 VAC  0.5A rating
OPERATING TEMPERATURE  -10°C to +60°C at 100% load, +70°C at 60% load
COOLING: Convection cooled
ISOLATION VOLTAGE: Input/Output – FG:  500VAC
SAFETY: EN60950, UL1950, EN60529 IP20 cat.
EMI: N/A
WEIGHT: 470g
DIMENSIONS: 50 x 97 x 110mm (W x H x D)
MOUNTING: DIN rail or Panel Mount
CONNECTOR: Screw treminal

Related Products