TDK – Lambda  GEN2.4 kW – Laboratory Power Supplies: 2.4 kW

The Genesys – TDK Lambda 1U Full-Rack (GEN-1U) series of 2400W DC Programmable Power Supplies provides high power density (up to 2400W) with a complete set of user-friendly interfaces within a 1U (1.75″) profile.

This series offers Output voltages from 8V (@ 300A) to 600V (@ 4.0A) in both Single-phase 230VAC Input (175-265VAC, 47-63Hz) with Active Power-Factor Correction (0.99 @ rated load) and Three-phase 208VAC Input (175-265VAC, 47-63Hz) with Active Power-Factor Correction (0.94 @ rated load) and two Auxiliary Outputs (15.0V @ 0.2A and 5.0V @ 0.2A) for use with Remote Analog Control/Status.

Multiple remote programming methods are available including the built-in Remote Analog Program/Monitor and Remote Digital Serial Communication (RS-232/RS-485) Interfaces along with the optional LXI certified LAN, IEEE (IEEE 488.2 & SCPI compliant) and Isolated Analog (5V/10V and 4-20mA) Interfaces.

SERIES TABLE

Model Output Voltage (VDC) Output Current ( A ) Output Power ( W )
GEN 8-300 0~8V 0~300 2400
GEN 10-240 0~10V 0~240 2400
GEN 16-150 0~16V 0~150 2400
GEN 20-120 0~20V 0~120 2400
GEN 30-80 0~30V 0~80 2400
GEN 40-60 0~40V 0~60 2400
GEN 60-40 0~60V 0~40 2400
GEN 80-30 0~80V 0~30 2400
GEN 100-24 0~100V 0~24 2400
GEN 150-16 0~150V 0~16 2400
GEN 300-8 0~300V 0~8 2400
GEN 600-4 0~600V 0~4 2400

SPECIFICATIONS TABLE

Input Voltage / Frequency (range) Single Phase,230V models: 170~265Vac, 47~63Hz,3-Phase, 208V models: 170~265Vac,  47~63Hz
Inrush Current Single-Phase and 3-Phase 208V models: Less than 50A
Power Factor Single Phase models: 0.99@230Vac, rated output power. 3-Phase models: 0.94@208Vac, rated output power.
Parallel Operation Up to 4 identical units in master/slave mode
Series Operation Up to 2 identical units. with external diodes. 600V Max to Chassis ground
Operating temp 0~50°C, 100% load.
Storage temp -20~85°C
Operating humidity 20~90% RH (non-condensing).
Storage humidity 10~95% RH (non-condensing).
Vibration MIL-810F, method 514.5 , The EUT is fixed to the vibrating surface.
Shock Less than 20G , half sine, 11mSec. Unit is unpacked.
Altitude Operating: 10000ft (3000m), Derate output current by 2%/100m above 2000m, Alternatively, derate maximum ambient temp.
by 1ºC/100m above 2000m. Non operating: 40000ft (12000m).
RoHS Compliance Complies with the requirements of RoHS directive.