GENERAL | |
EMC (immunity) | EN 61000-4-2 / EN 61000-4-3 / EN 61000-4-4 / EN 61000-4-5 / EN 61000-4-6 / EN 61000-4-8 |
EMC (emission) (class) | EN 55022 (B) |
Safety | EN62040-1 |
Cooling / Isolation | Forced / Doubled |
MTBF | 240 000 hrs (MIL-217-F) |
Efficiency (Typical): Enhanced power conversion / on line | 96% / 91% |
Dielectric strength DC/AC | 4300 Vdc |
True Redundant Systems – compliant | 3 disconnection levels on AC out and DC in power ports 4 disconnection levels on AC in port |
RoHS | Compliant |
Vibration | GR63 office vibration 0 to 100 hz-0.1 g / transport vibration 5-100 Hz 0.5 g 100 to 500 hz-1.5 g / Drop test |
Operating conditions | Designed for installation in an IP20 or IP21 environment. When installed in a dusty or humid environment, appropriate measures (air filtering, …) must be taken. |
Altitude above sea without de-rating | < 1500 m / derating > 1500 m – 0.8 % per 100 m |
Ambient / storage temperature / relative humidity | -20 to 50 ° C / -40 to 70 ° C / 95 %, non-condensing |
Material (casing) | Coated steel-ALU ZINC |
AC OUTPUT POWER | |
Nominal Output power (VA) / (W) | 2500 / 2000 |
Short time overload capacity | 150 % (15 seconds) 110 % permanent within T° range |
Admissible load power factor | Full power rating from 0 inductive to 0 capacitive |
Internal temperature management and switch off | Yes |
DC INPUT SPECIFICATIONS | |
Nominal voltage (DC) | 110Vdc |
Voltage range (DC) | 90 – 160 Vdc |
Nominal current | 19 A (at 110 Vdc and 2000 W output) |
Maximum input current (for 15 second) / voltage ripple | 29 A / < 200 mV rms |
Input voltage boundaries | User selectable with T2S interface |
AC INPUT SPECIFICATIONS | |
Nominal voltage (AC) | 220/230/240 V 1P or 3P (Min 3 shelves for 3P) |
Voltage range (AC) | 150-265 V |
Brownout | 150 to 185 V linear derating 150 VA/120 Watts per 10 Vac |
| 2000 VA/1600 W @ 150 Vac |
Conformity range before transfer to DC | Adjustable |
Power factor | > 99% |
Frequency range (selectable) / synchronization range | 50 – 60 Hz / range 47 – 53 Hz / 57 – 63 Hz |
AC OUTPUT SPECIFICATIONS | |
Nominal voltage (AC*) | 220/230/240 V |
Frequency / frequency accuracy | 50 – 60 Hz / 0.03 % |
Total harmonic distortion (resistive load) | < 1.5 % |
Load impact recovery time | 0.4 ms |
Turn on delay | 20 s to 40 s depending on the number of module installed |
Nominal current. Protected against reverse current | 10.9 A |