MEDIA is a compact and scalable modular inverter providing a pure sine wave AC supply. In conjunction with a DC Power system, it provides an excellent AC backup solution. It uses the latest inverter technology, providing superior energy
efficiency in a compact size.

The “Twin Sine Innovation” (TSI) technology eliminates all single points of failure with full scalability; up to 32 modules in parallel and high efficiency of up to 95% reducing operating costs.

 

Monitoring Unit T2S ETH

Compatible with : TSI Nova, Media, Bravo & ECI Bravo modular inverters

Supported Protocols

  • Modbus RTU ( read only )
  • SNMP ( read only)

Logs

  • Event log up to 2000 events

System Features

  • 3 output relays (Major, Minor and one user programmable)
  • 2 digital inputs
  • ETH connection
  • 3 status LED (Red – Major, Orange – Minor, Green – OK)
  • CET Module bus
  • Rack mounting
  • 12 V power supply from shelf
  • RS485 for Modbus

 

SPECIFICATIONS TABLE

Specifications
48 / 230
POWER1.5 kVA
INPUT48 Vdc
OUTPUT230 Vac
Nominal voltage (DC)48 V
Voltage range (DC)40 – 60 V
Nominal current (at 48 Vdc and 1200 W output)28 A
Maximum input current (for 15 second) /
Voltage ripple (resistive load 54 Vdc)
48 A / < 2 mV
Nominal voltage (AC)220/230/240 V 1P or 3P (min 3 shelves for 3P)
Voltage range (AC)150 – 256 V
Power factor>99%
Frequency / frequency accuracy50 – 60 Hz / range 47 – 53 Hz / 57 – 63 Hz
EMC (immunity)EN 61000-4-2 / EN 61000-4-3 / EN 61000-4-4 / EN 61000-4-5 / EN 61000-4-6 / EN 61000-4-8
DisplaySynoptic LED
Cooling / IsolationForced / Doubled
Alarms output / supervisionDry contacts on shelf / Standard USB port and MODBUS on T2S, optional : Candis Display / Candis TCP-IP

Ask for Assistance

Selecting the right power supply for your application is not a small task. Let our technical sales engineers guide you through the process of choosing the right solution for your needs.

Below some parameters usually required to size and select the right power supply:

  • Power & control requirements
  • Output & Input Voltage / Multioutput Voltage / Variable Voltage
  • Redundancy level
  • Mounting
  • Inrush Current
  • Environmental specifications (Temperature, altitude, vibration, shock)
  • Specific Industries Standards (Railway, Military, Medical)