MPS Ultra

2U Redundant Hot Swap Modular DC Power System

The 2RU MPS Ultra DC power system from ICT delivers up to 5.6 kilowatts of power in three factory pre-configured systems that make installation and setup a breeze.Available for 48, 24 or 12 volt DC applications, MPS Ultra systems are preconfigured at the factory to provide fast, easy installation at the site. With Ethernet-based remote monitoring and DC power control, advanced battery management features, integrated dual 100A battery breakers, and up to 12 fully managed load outputs that can be monitored and power-cycled remotely, the MPS Ultra provides unmatched capability for demanding wireless applications.

Power Chassis

  • 2RU Power Chassis configured at factory for fast, easy installation
  • All connections are accessible from the rear, there are no covers to remove during setup
  • Accepts 48, 24 or 12 volt DC hot-swappable ICT 700 watt
    Power Modules (depending on model)

Integrated Intelligent Control Module

  • TCP/IP remote Ethernet communications for monitoring and control of all system parameters through a single I.P. address and fully integrated user interface
  • Embedded web server for plug and play set up
  • HTTP/HTTPS, SMTP, SNMPv1/v2c/v3 protocols supported
  • Alarms can be sent to multiple email accounts
  • Four site monitoring sensor inputs with alarm reporting
  • Data logging of AC, DC, alarms and load current conditions
  • Password protection with multiple security levels
  • AC input voltage, DC output voltage, system current reporting (local
    and Ethernet)

Load Distribution Features (2.8 & 3.5kW and 4.2kW models)

  • Load current monitoring and alarm reporting of each output for pinpointing of issues with connected loads
  • Outputs can be power cycled individually over Ethernet
  • Adjustable alarm and load-shed settings for each output
  • Max 30A circuit breakers

Battery Management Features (2.8 and 3.5KW models)

  • Temperature-compensated charging, display of battery voltage, status, battery current, state of charge, and run time remaining
  • Adjust LVD settings remotely
  • Configure advanced battery management features such as boost charge parameters, max charge current, battery capacity, battery test timer, and battery discharge testing

700 Watt Power Modules (order separately)

  • 100-300 volts AC input with Power Factor Correction
  • 48, 24 or 12VDC volts nominal DC output
  • 90-93% efficiency
  • -30 to +60C operating temperature range

Specifications Table

AC INPUT
Nominal system voltage 120/240VAC
Input voltage range 100-300VAC
Power factor (typical) 0.99
Frequency 50/60Hz
DC OUTPUT
Check Out Datasheet Above
MECHANICAL
AC input connector Terminal Block, #8 – #16 AWG
DC output connector Busbars with 5/16” bolts
Remote alarm connectors Terminal Block (#16 -24 AWG)
Mounting 2RU, 19 in rack mount
Weight (Exc.Power Modules) 30lbs / 13.6 kg
Dimensions – H X W X L  3.5 x 19.0 x 15.7 in. / 89 x 483 x 398 mm
ENVIRONMENTAL
Operating temperature range  -30º to +60ºC
Output derating 2% / ºC (above 50º C)
Storage temperature  -45º to +85ºC
COMMUNICATIONS & CONTROL
Front Display High resolution OLED with function keys
Remote Communications TCP/IP 10/100 Base-T
I.P. Protocols HTTP/HTTPS, SMTP, SNMPv1/v2c/v3
Inputs 4 digital, 1 analog temp sensor contacts