The Multi Guard Industrial range was specially developed to ensure power continuity in all sectors deemed critical due to the specific environmental conditions or industrial processes requiring protection.Multi Guard Industrial is available in a 20 kVA stand alone version and in modular versions from 20 to 160 kVA. The two versions are available in both single-phase and three-phase output configurations. This high level of flexibility allows Multi Guard Industrial to accept both single-phase and three-phase inputs with no need for special set ups or operator intervention, ensuring full compatibility with any power supply network.

 

SERIES TABLE

MODEL  NUMBER PHASES OUTPUT BYPASS VOLTAGE  OUTPUT VOLTAGE 
GMI M 1 380-400-415 Vac, three-phase + N 220-230-240 Vac, single-phase + N (selectable)
GMI T 3 380-400-415 Vac, three-phase + N 380-400-415 Vac, three-phase + N (selectable)

SPECIFICATIONS TABLE

INPUT
Voltage 380-400-415 Vac, three-phase + N and 220-230-240 Vac single-phase + N
(input voltage recognition function)
Voltage tolerance  -40/20%
Frequency 50/60 Hz
Frequency tolerance 40 – 72 Hz
Power factor at full load > 0.99
Current distorsion thdi ≤ 3%
BY PASS
Nominal Voltage see series table
Voltage tolerance 180 – 264 V (selectable) referring to neutral phase
Bypass Overload 125% for 60 minutes, 150% for 10 minute
OUTPUT
Voltage see series table
Voltage stability ≤ 1%
Frequency 50 Hz / 60 Hz
UPS MODULE
Power 20 kVA / 18 kW
Output power 20 kVA x number of modules, up to a maximum of 8 (max. 160 kVA)
BATTERIES
Layout independent batteries for each UPS module or shared by the UPS system
Type VRLA AGM/GEL
Recharge time 6 hours