OPUS HE DC power systems consist of MHE rectifiers, VIDI+ controllers, Connections for mains and battery and load distribution. System is configurable to match with requirements of the application.
System is configurable to match with requirements of the application. 19” 12U Rack delivers maximum 10 kW output power at 48, 60, 110, 125 and 220 VDC and 7.5 kW at 24 VDC output. 19” 12U Racks include slots for maximum 5 rectifier modules. Load distribution configuration of MCB quantity and current ratings can be configured per order. Wall mounting, IP21 cover kit, temperature sensor, battery block voltage monitoring and BLVD are options.
NETWORK MANAGEMENT PROTOCOLS |
---|
Model | Power Out Max (kW) | Input Voltage (VAC) | Output Voltage Range (VDC) | Output Current Max (A) |
OPUS HE 24-4.5 R12U F | 7.5kW | 100-250 VAC / 3 x 173-433 VAC (TN-S system)* | 21-33VDC | 312.5A |
OPUS HE 48-6.0 R12U F/P | 10kW | 100-250 VAC / 3 x 173-433 VAC (TN-S system)* | 42-59VDC | 208.5A |
OPUS HE 60-6.0 R12U F/P | 10kW | 100-250 VAC / 3 x 173-433 VAC (TN-S system)* | 51-72VDC | 166.7A |
OPUS HE 110-6.0 R12U F | 10kW | 100-250 VAC / 3 x 173-433 VAC (TN-S system)* | 90-150VDC | 92.5A |
OPUS HE 125-6.0 R12U F | 10kW | 100-250 VAC / 3 x 173-433 VAC (TN-S system)* | 100-160VDC | 83.3A |
OPUS HE 220-6.0 R12U F | 10kW | 100-250 VAC / 3 x 173-433 VAC (TN-S system)* | 178-280VDC | 46.3A |
*Options: 1-phase supply 100-250VAC, 3-phase Delta/IT supply 3 x 173-250VAC |
AC-connection | TN-S system, 3W + N + PE, (3-phases, neutral and protective earth wires) |
Nominal voltage | 100-250 VAC / 3 x 173-433 VAC (TN-S system) |
Cooling | Natural convection |
Protection | IP 20 Option IP21 |
Controller user interface | Display and local control in front panel |
Distribution and Connections | Behind front panel |
Colour | Frame RAL 7012 |
Dimensions, rack mounting | Height 12U (533 mm) Width 482 mm Depth 395 mm |
Operating temperature | -25°C … +60°C |
Humidity max | 95% relative humidity, non-condensing |
Altitude max | Max 3km, full power up to 2km above sea level Derating 1% per 100 m between 2-3km |
Safety | Rack: EN61439-1, EN61439-2 Rectifiers: EN 62368-1, EN 50124-1 rail |
EMC | Rack: EN61439-1, EN61439-2 Rectifiers: EN61000-6-1 / -2 / -3 / -4 Generic EN61000-6-5 EN 50121-4 Rail, ETSI EN 300 386 (48/60V) |
Selecting the right power supply for your application is not a small task. Let our technical sales engineers guide you through the process of choosing the right solution for your needs.
Below some parameters usually required to size and select the right power supply:
Contact our team of experienced engineers to discuss your unique power conversion and backup needs. We offer a wide range of highly reliable components that can be integrated and customized to create a solution that meets or exceeds your requirements.
For power automation systems please contact us at power.systems.automation@heliosps.com.au
© Copyright Helios Power Solutions 2023