  • Input PF > 0.99, THDi < 4 % (without additional filters)
  • Output PF up to unity and compatible with inductive or capacitive loads without derating
  • Ingress protection up to IP43 (more rugged environmental protection available upon request)
  • Integrated static and manual bypass lines
  • Parallel capability up to 160 kVA (4 x 40 kVA in parallel)**
  • 7″ color Touch Screen graphic
  • Connectivity options: SNMP, Modbus, BACnet®
  • Phase configuration options: 1/1, 3/1 and 3/3
  • Large set of functional options to meet all specific requirements and challenging conditions

 

Specifications

INPUT
Rectifier type IGBT based, Vienna bridge
Nominal voltage (3 phase+N+G) 380/400/415 I Only with 10 kVA/kW Power Module: (1 phase+N+G) 220/230/240
Voltage range (V) 304 to 478 V (at full load) I 228 to 304 V (with load decreasing linearly)
Frequency (Hz) 50/60
Frequency range (Hz) 40/70
Input power factor > 0.99
Input THDi < 4 % (with full linear load)
OUTPUT
Inverter type 3-level IGBT based
Voltage (V) (3 phase) 380/400/415 I Only with 10 kVA/kW Power Module: (1 phase+N+G) 220/230/240
Output THDv (according to IEC EN 62040-3) < 1 % (with linear load)
< 5.5 % (with non linear load)
Output PF Up to 1
Crest factor 3:01
Frequency (Hz) 50/60
Overload capacity (through inverter line) 110 % for 60 min
125 % for 10 min
150 % for 1 min
> 151 % for 200 ms
AC/AC efficiency in double conversion (VFI) > 94 % (at nominal load)
AC/AC efficiency in ECO Mode (VFD) > 98 % (at nominal load)
BATTERY LINE
Nominal DC voltage (VDC) ± 240 (with +/N/- connections)
Number of cells 240 (settable from 192 to 264)
Recharge power 10 % * System Power (nominal value); settable: from 0 to 20 % * System power
ENVIRONMENTAL
Operating temperature (°C) 0 to 40
Storage temperature (°C) -40 to 70
Relative humidity 0 to 95 %
Altitude Up to 1000 m (without derating), up to 2000 m (load derated 1 % every 100 m)
Noise at 1 m distance at 100 % of load (dB) 66

Cabinet Power table

CABINET 20 30 40
Maximum power capacity (kVA/kW) 20/20 30/30 40/40
Maximum number of power modules connected 2 x 10 kVA 2 x 15 kVA 4 x 10 kVA
Dimensions with IP20, W x D x H (mm) 600 x 800 x 1810
Weight of standard cabinet IP20 without transformer (kg) 165 165 172
Phase configuration 3/3; 3/1; 1/1 3/3; 3/3; 3/1; 1/1
Color of the frame RAL 7035 RAL 7035 RAL 7035
Ventilation Dual ventilation system: In each power module with inbuilt fan fault detection and inside the cabinet (forced ventilation from front to top)

Power Modules Specifications

POWER MODULE 10 KVA/KW
Dimensions W x D x H (mm) 438 x 590 x 85 (2U)
Weight (kg) 15.3
POWER MODULE 15 KVA/KW
Dimensions W x D x H (mm) 438 x 590 x 85 (2U)
Weight (kg) 15.5