DIN Series DC Power Distribution Unit 60A

Brand: ICT Power

SKU: ICT-DIN-PDU6
This product is available globally.
  • 60-amp continuous system current
  • Six DC load outputs each rated at 15A max
  • Each output is GMT fuse-protected
  • Supports HTTPS, SMTP, TLS1.2 and SNMPv3 protocols
  • Remote alarm report for each load output including fuse trip, voltage and current deviations
  • Software Demonstration of DIN Series PDU

Product Range

SKU Type of Protection OTHER FEATURES
DINICT-DIN-PDU6FusesNetworking

Description

DIN Series DC Power Distribution Unit

Single Bus DC Distribution Module for 12V, 24V or 48V applications

The DIN Series Power Distribution Unit from ICT is a DIN-rail mount, single-bus DC distribution module designed to be used in 12V, 24V or 48V DC applications.  It includes a secure, easy-to-use web-browser interface, which provides remote power monitoring, power control, and alarm reporting over an Ethernet link, along with SNMP support for integration into your network management system.

Combined with the ICT DIN 360-watt DC UPS, remote monitoring and control of battery current and voltage, low voltage disconnect setpoints, and battery charge current settings are available through the ethernet controller and user interface.

DIN Rail DC UPS and Power Distribution Unit 24V 48V
Fully remote monitored and managed DC power and distribution solution over Ethernet

Benefits

  • Full remote monitoring and power control reduces site visits, lowering total cost of ownership and maintenance costs
  • Improve the quality of service and uptime of your network by quickly resolving power issues remotely
  • Increase battery backup time with automatic load shedding by allowing non-critical loads to be removed from the system, maintaining critical loads for longer
  • No additional software required as monitoring and control is provided via an onboard web-based server
  • Front-mounted fuses allow for quick and easy replacement

Additional information

Weight1.22 kg
Dimensions111 × 134 × 144 mm

Specifications Table

Electrical

Power Specifications ICT-DIN-PDU6
Nominal Application Voltage12,24 and 48VDC
Operation Voltage Range+10 to +60VDC
Bus Current Rating (Continuous)60A
Output Current Rating12A
Number of GMT Fused DC Outputs6
GMT Fuse Rating (Max)15A15A

Communications

EthernetTCP/IP built-in web server and graphical user interface, 10/100BASE-T, IEEE 802.3 compatible
Supported ProtocolsIPv4, HTTP, HTTPS, SMTP, DNS, TCP, UDP, ICMP, DHCP, ARP, SNMPv1/v2c/v3
SNMP PortsUDP Port 161, SNMP Traps: UDP Port 162
Firmware UpgradesUpgradeable over Ethernet
SecurityPassword protection, HTTPS encryption, TLS 1.2
Load Output MonitoringCurrent draw measured and reported for each output, user definable under and over current alarms
Email and SMS AlertsMultiple email or text accounts, adjustable intervals
Data LoggingUp to 30 days at 1 minute sampling rate, csv file download, major event logging
Network WatchdogAutonomously ping up to six IP addresses and power-cycle output if no response, definable settings
Power Cycling and RebootingRemote on/off control of every output individually
Auto Restore ModeReturn to previous output settings after a power loss
Power-up Delay SequencingUser selectable 0 to 60 second delay between outputs
Auto Load SheddingEach output user definable, manual or auto restart

View Datasheet