The Distribution Series 3 Dual Bus DC Distribution Panels are designed to be used in 12, 24 or 48VDC applications. All models feature either 12 fuse- or breaker-protected outputs (model dependent) with ATO FKS 80 volt rated fuses, or hydraulic/magnetic breakers (breakers sold separately). Dual voltages and polarities can be run simultaneously.

Each independent bus has six outputs rated at up to 25 amps max (at 12/24VDC), or 15 amps max (at 48VDC). Fused models feature LED indicators on the front panel, enabling easy identification and replacement of blown fuses.An integrated security protected Ethernet communications port (select models) allows the panel to be monitored from a remote site using an industry standard web browser. HTTPS and SNMP V1/V2c protocols are supported. System current, system voltage, individual output currents and breaker status can be monitored, and alarms can be sent to multiple email accounts.

DC outputs can be turned on and off remotely (select models), allowing connected loads to be power-cycled using the Ethernet connection. Automatic load-shedding can be defined to protect critical loads. A network watchdog feature will ping up to two IP addresses and power-cycle loads such as routers which may need rebooting to restore communications with the site.The 1RU design saves valuable rack space, and fits all standard 19 inch racks. Each bus has its own independent Form C alarm contacts.

SERIES TABLE

Model Description Application Voltage (pos or neg ground) System Current Rating (peak/cont)
ICT200DF-12 Standard Dual Bus
Fuse Panel
12, 24, 48VDC 200A/160A
ICT200DB-12 Standard Dual Bus
Breaker Panel
12, 24, 48VDC 200A/160A
ICT200DF-12IRC Intelligent Dual Bus
Fuse Panel With TCP/IP
12, 24, 48VDC 200A/160A
ICT200DB-12IRC Intelliigent Dual Bus
Breaker Panel With TCP/IP
12, 24, 48VDC 200A/160A

SPECIFICATIONS TABLE

Power Specifications
Application Voltage (pos or neg ground) 12, 24, 48VDC
System Current Rating  (peak/cont) 200A/160A
Bus Current Rating (peak/cont) 100A/80A
Number of Outputs per bus 6
Mechanical
Form Factor 1RU – 19 Inch rack mount with handles
Dimensions (inches) L x W x H 9.29 x 19.0 x 1.72
Weight (lbs/kg) 7.0 lbs / 3.2 kg
Connectors M8 DC input stud connectors, 10-22AWG cage clamp output terminal blocks
Environment
Operating Temperature Range -30oC to +60oC