The SR SmartCharger is designed to recharge your battery in the shortest practicable time with programmable parameters to suit your specific application.Smartcharger 250W

SERIES TABLE

Model Output Voltage¹ (float) Output Voltage¹ (max boost) Output Current (continuous) Min – Max Battery Size2
SR250E12 13.8 14.7 16.7A 65-200 Ah
SR250E24 27.6 29.4 8.3A 30-100 Ah
SR250E36 41.4 44.1 5.6A 22-70 Ah
SR250E48 55.2 58.8 4.2A 15-50 Ah
¹ May be adjusted to suit battery specifications
²  Guidelines only.   Please check manufacturer’s recommendations.

SPECIFICATIONS TABLE

ELECTRICAL
Input STANDARD: 180V – 264VAC
OPTIONAL: 88V – 132VAC
Frecuency 45-65Hz
Fusing Internal AC input fuse
Isolation 1KV DC input – output / earth
Efficiency > 85%
Inrush current Soft start circuit
Output power 250W
Output voltages Refer to the model table
Voltage adj. range Approx 95 – 105% of V nominal
Temp. Compensation Temperature sensor on 1.7m lead with
adhesive pad:  -4mV / °C / cell ±10%
Current Limit Constant current limit on overload & short circuit
Output Protection Automatic shutdown if battery leads reversed
or short circuit on output
Line regulation < 0.2% over AC input range
Load regulation < 0.4% open circuit to 100% load
Noise <1%
Drift 0.03% / °C
Hold-up time 15 – 20 ms (nom. – max. Vin) without  battery
OVP Over-voltage protection on output at ~ 130% of nominal output voltage
Thermal Protection Yes
Alarm & boost/float indication relays* Mains fail
Batt low (set at 1.83V/cell = 11, 22V, etc)
Boost/float
Alarm Relay Contacts C – NO – NC  full changeover   Rated 1A @ 50V DC or 32VAC
Adjustable Parameters All firmware parameters listed under features may be adjusted at time of ordering
FEATURES
Switch/ LED Indication & functions BOOST:  Red
FLOAT:  Green
STANDBY: Red (Push button to turn output off/on).
Refer to instruction manual  for full list of LED Operation codes
Factory Programmable parameters (default settings shown in brackets; please note that some parameters are interdependent of each other) Start up in boost or float mode (Boost)
Current terminated boost  (Yes)
Current initiated boost  (Yes)
Start boost on mains return (Yes)
Pre-boost state timer 1-255 minutes (1)
Max boost charge time 0-48 hours (24)
Pre-float state timer 1-255 minutes (1)
Resume prior state upon mains return timer 1-255 minutes (10)
Resume on boost charge upon mains return 0-255 hours (24)
Pre-forced float timer 1-255 minutes (1)
Delay before mains fail recognition 4sec – 8.5minutes(5 minutes)