AC/DC Rail Din Power Supply up to 480 W.
Model | Input | Output | Power |
DNR120AS12-I | 90 to 132/180 to 264 Vac | 12 V / 10 A | 120W |
DNR120AS24-I | 90 to 132/180 to 264 Vac | 24 V / 5 A | 120W |
DNR120AS48-I | 90 to 132/180 to 264 Vac | 48 V / 2.5 A | 120W |
DNR240PS24-I | 90 to 132/180 to 264 Vac | 24 V / 10 A | 240W |
DNR240PS48-I | 90 to 132/180 to 264 Vac | 48 V / 5 A | 240W |
DNR480PS24-I | 90 to 264 Vac, 120 to 375 Vdc | 24 V / 20 A | 480W |
DNR480PS48-I | 90 to 264 Vac, 120 to 375 Vdc | 48 V / 10 A | 480W |
Dimensions: | DNR120: 4.57 x 2.50 x 4.92 in (116.0 x 63.5 x 125.0 mm) |
DNR480: 4.39 x 3.27 x 4.92 in (111.3 x 83.0 x 125.0 mm) | |
Input Voltage: | 90-132/180-264 VAC, auto select, |
210-375 VDC (DNR120AS, DNR240PS) | |
90-264 VAC, 120-375 VDC (DNR480PS) | |
Harmonic Currents: | EN61000-3-2, class A |
Efficiency: | 84-90% |
Operating Temp: | DNR120: -35 °C to +70 °C, derate linearly from +60 °C at 2.5%/°C, start up at -30 °C |
DNR240: -40 °C to +70 °C, derate linearly from +60 °C at 2.5%/°C, start up at -35 °C | |
DNR480: -40 °C to +70 °C, derate linearly from +55 °C at 2.5%/°C, start up at -35 °C, see datasheet | |
Isolation: | 3000 VAC Input to Output |
1500 VAC Input to Ground | |
500 VAC Output to Ground | |
European Safety Approvals: | EN60950-1, CE Mark |
US Safety Approvals: | UL508 UL60950-1, cUL60950-1 Pollution Degree 2,UL60950-1 Overvoltage Category II, UL508 Overvoltage Category III, ANSI/ISA 12.12.01. (Class 1, Division 2, Groups A,B,C and D) |
EMC: | EN55022, class B conducted & radiated |