48Vdc Modular Battery Charger with front-accessible fuse distribution

1U Integrated Shelf System with GMT Distribution

The SOL Series High-Performance (HP) rectifiers make a proven, reliable platform even better, with significant advancements in efficiency and performance. Featuring a compact, fan-cooled design, HP rectifiers open the possibility to wider ranges of applications and immediate Op-Ex/Cap-Ex savings, reducing total cost of ownership and impact on the environment. Designed specifically for restricted space installations, this 48Vdc power and distribution system incorporates the reliable 48V, 1.2kW Cordex rectifier modules and front-accessible fuse distribution connections.

The system is a perfect solution for small 48Vdc power applications such as customer premise, xDSL, FTTx, distributed node B and microwave. High efficiency, high temperature operation, and a small 1RU footprint make the system ideal for harsh outside plant installations. The 19″ universal rack mount power system accommodates up to three  HP 48V-1.2kW rectifiers and a modular  CXCM1 controller, with GMT Fuse distribution, in a compact 1RU package.

  • Rectifier power modules are “hot-swappable”—they can be inserted or removed from the shelf without cutting power to or from the system or the load.
  •  Additional power modules can be added to the system at the time of ordering or after the shelf has been installed.
  • The shelves are designed for horizontal mounting in a 19″ or 23″ centre mount (flush mount for 1RU shelves) installation via universal mounting brackets (EIA rack spacing) and utilize dual
    IEC-type connectors for multiple AC line cord solutions.
  • The CXCM1 HP was designed as a modular, high-performance controller for the rectifier series.
  • All controllers models allow the user to set up, control and monitor the entire power system and ancillary components from one central, easy-to-use source. Details of controller operation are
    provided in the current version software manual.
  •  The equipment is suitable for installation in network telecommunication facilities.

Controller:

NETWORK MANAGEMENT PROTOCOLS

SPECIFICATIONS TABLE

Electrical
Input Voltage:
Operating:90 to 300Vac
[See output power for power derating]
Input Current
(per module):
7.5A Maximum (176 to 300Vac)
6.0A Maximum (90 to 176Vac)
Efficiency:>93% at 240Vac Input and 40-100% load
Power output
(per module):
1200W (176 to 300Vac input)
600W (110 to 130Vac Input)
* Power de-rated linearly from 1200-600W
(176 to 130Vac input)
* Power de-rated linearly from 600-500W
(110 to 90Vac input)
Current output
(per module):
 25A@ 48Vdc (176 to 300Vac input)
12.5A @ 48Vdc (110 to 130Vac Input)
Mechanical
19 & 19/23”
Dimensions:44H x 439.5W x 305D (mm)
1.75H x 17.3W x 12D (inches)
*Note: Excludes Recti er Front Handle and Optional Kydex Cover
Mounting:19” or 23” rack, 6” o set (center),
EIA rack spacing
Weight:
Shelf:3kg (6.6lbs)
Rectifier:1.23kgb (2.72lbs)
Connections
GMT Fuse (Load):
(7) Positions:Terminal block (#16 to #30 AWG)
(1) Position:Terminal block (#14 to #26 AWG)
Battery:¼” on ⅝” center 2-hole lugs
AC Input:Dual IEC-60320-C20 MAIC connectors
(for use with IEC-60320-C19 female line cords)
Alarms:Terminal block (#16 to #24 AWG)
Environmental
Temperature:
Standard: -40 to 65°C (-40 to 149°F)
Storage: -40 to 80°C (-40 to 176°F)
Extended: -40 to 80°C (-40 to 176°F)
(de-rated output power)
Humidity: 0 to 95% RH non-condensing
Elevation: -500 to 2800m (-1640 to 9186ft))
Cooling:Fan cooled (front to rear)
Heat Dissipation:.924 BTU hour/system max.
Standards
Safety:CSA C22.2 No 60950-1-03
CE marked
NEBS:GR-1089-CORE
GR-63-CORE
*Consult factory for certi cation status

Ask for Assistance

Selecting the right power supply for your application is not a small task. Let our technical sales engineers guide you through the process of choosing the right solution for your needs.

Below some parameters usually required to size and select the right power supply:

  • Power & control requirements
  • Output & Input Voltage / Multioutput Voltage / Variable Voltage
  • Redundancy level
  • Mounting
  • Inrush Current
  • Environmental specifications (Temperature, altitude, vibration, shock)
  • Specific Industries Standards (Railway, Military, Medical)
  • Terminals

Contact Our Team

Contact our team of experienced engineers to discuss your unique power conversion and backup needs. We offer a wide range of highly reliable components that can be integrated and customized to create a solution that meets or exceeds your requirements.

For power automation systems please contact us at power.systems.automation@heliosps.com.au