Our website features a wide range of standard power conversion and backup products, but we also have the capacity and capability to design and manufacture custom solutions to meet your specific application needs. Contact our team of experienced engineers today to discuss your project. Dismiss
Switch Mode
Modular Rectifiers
N+1
Redundancy
Modbus TCP/IP
IEC 61850 Adapter
Battery & Load
Distribution
Battery
Management
No
Fan
OPUS HE DC power systems consist of MHE rectifiers, VIDI2 controllers, Connections for mains and battery and load distribution. System is configurable to match with requirements of the application. The base system supports up to three (3) MHE series high efficiency rectifiers, but may be expanded by using the 5U Slave Rack in a master-slave configuration, increasing the power capability to 16 kW.
Optional accessories include 19″ load distribution panels, wall-mounting kit, IP21 cover kit, temperature sensor and Battery LVD
.
NETWORK MANAGEMENT PROTOCOLS |
---|
MODEL NUMBER | POWER OUT MAX (KW) | INPUT VOLTAGE (VAC) | OUTPUT VOLTAGE RANGE (VDC) | OUTPUT CURRENT MAX (A) |
OPUS HE 24-4.5 5U F | 4.5 | 100 – 250 | 21 – 33 | 187.5 |
OPUS HE 48-6.0 R5U F | 6 | 100 – 250 | 42 – 59 | 125 |
OPUS HE 60-6.0 R5U F | 6 | 100 – 250 | 51 – 72 | 100 |
OPUS HE 110-6.0 R5U F | 6 | 100 – 250 | 90 – 150 | 55.5 |
OPUS HE 125-6.0 R5U F | 6 | 100 – 250 | 100 – 160 | 50 |
OPUS HE 220-6.0 R5U F | 6 | 100 – 250 | 178 – 280 | 27.8 |
AC-connection | TN-S system, 3W + N + PE, (3-phases, neutral and protective earth wires) |
Nominal voltage | 220-240 VAC / 3 x 380-415 VAC (TN-S system) Options: 1-phase supply 100-250VAC, 3-phase Delta/IT supply 3 x 173-250VAC |
Cooling | Natural convection |
Protection | IP 20 Option IP21 |
Controller user interface | Display and local control in front panel |
Distribution and Connections | Behind front panel |
Colour | Frame RAL 7012 |
Dimensions, rack mounting | Height 5U (222 mm) Width 19” (482 mm) Depth 380 mm Weight 15 kg w/o rectifiers |
Operating temperature | -25 … +60°C, see derating, Start-up at -40°C |
Humidity max | 95% relative humidity, non-condensing |
Altitude max | Max 3km, full power up to 2km above sea level Derating 1% per 100 m between 2-3km |
Safety | Rack: EN61439-1, EN61439-2 Rectifiers: EN 62368-1, EN 50124-1 rail |
EMC | Rack: EN61439-1, EN61439-2 Rectifiers: EN61000-6-1 / -2 / -3 / -4 Generic EN61000-6-5 Utility, surge level 2 EN 50121-4/-5 Rail, ETSI EN 300 386 (48/60V) |
Selecting the right power supply for your application is not a small task. Let our technical sales engineers guide you through the process of choosing the right solution for your needs.
Below some parameters usually required to size and select the right power supply:
Contact our team of experienced engineers to discuss your unique power conversion and backup needs. We offer a wide range of highly reliable components that can be integrated and customized to create a solution that meets or exceeds your requirements.
For power automation systems please contact us at power.systems.automation@heliosps.com.au